Customization: | Available |
---|---|
Brand: | Korno |
Customized: | Customized |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Product Description:
The DN1000 series gas alarm controller can be applied to the measurement and control of various signals, such as 4-20mA signals, RS-485 signals, and TCP/IP network interface devices.
The electronic circuit adopts advanced high precision micro-controller processing technology, which makes the controller work stably with high measuring precision and strong generality.
The system adopts Andriod operating system. Therefore, it has user-friendly operation interface, powerful system function. Operating the system menu through buttons, the main display screen displays gas detector concentration value, alarm information, fault information and other information.
• standard 4-20mA signals input, supports up to 8 detectors input
• standard Modbus RS-485 signal input, supports up to 8 detectors input
• standard TCP/IP network port device input
• 32G mass data storage,TF card data export, data printing
• 2 relays outputs as standard,each relay out can control one jet fan
• RS485, multi-channel 4-20mA signal, TCP/IP network port output
• split-screen display function, each screen display related data of 8 channel
Product name | Gas Alarm Controller |
Product model | DN1000 |
Working power | 220VAC |
Standby power supply | 24VDC |
Work mode | inspection |
Input signal | 4 ~ 20mA signal (two-wire or three-wire gas detector); Modbus RS485 signal; TCP / IP network port equipment optional |
Output signal | RS-4854, TCP / IP network port output, multi-channel 4 ~ 20mA signal output (optional) |
Alarm record | with status bar information alarm prompt function, with alarm record query function |
Alarm alarm set | the alarm set, the normal alarm settings: A1 alarm, A2 alarm, A3 alarm; interval alarm settings: AL alarm point, AH alarm point |
Alarm output | 2 group of public relays set the alarm output of each device |
Contact capacity | 220VAC, 10A |
Communication interface | RS-485 MODBUS; Ethernet port |
Operating temperature | -20 ºC - 55 ºC |
Operating humidity | 0-90% relative humidity (no condensation) |
Environmental pressure | 86 ~ 100kPa |
Display | 3.5-inch LCD screen |
Measurement accuracy | ≤ ± 1% |
Housing material | SPCC (304 stainless steel is optical) |
Dimensions | 280mm (L)× 88mm (H)× 200mm(W) |
Weight | 4KG |
Alarm mode | sound alarm, red LED alarm light, short distance wireless alarm transmission |
Button operation | with muffler, lock screen, flip three key operation |
Direct reading | measured value |
Data records | automatically stored the data is available optional micro TF memory card |
Calibration | supports 4mA, 20mA current calibration operation |
Protection class | IP54 |
Operating mode | User mode, administrator mode are available |
Implementation of the standard | GB 16808-2008 |